Charged with FK-5-1-12, this extinguisher discharges a liquid that flashes into an electrically non-conductive gas. It rapidly suppresses Class A, B, and C fires and leaves absolutely zero residue behind, ensuring that servers, medical imaging machines, and lab equipment survive both the fire and the suppression effort.
MRI-Safe Construction Unlike standard steel extinguishers that pose extreme physical hazards near strong magnets, the CA14-NM is built with a specialized stainless steel shell and an MR Conditional valve, hose, and nozzle. It has been strictly tested to 7.0 Tesla, making it entirely safe to mount and deploy directly inside active MRI suites.
Ideal Applications:
Hospital MRI and medical imaging suites
Data centers and server rooms
Telecommunications facilities
Advanced research laboratories
Cleanrooms
Technical Specifications:
Model: CA14-NM (Part No. 443479)
UL/ULC Fire Rating: 1-A:10-B:C
Agent Type: FK-5-1-12 Clean Agent
Agent Capacity: 14 lbs (6.35 kg)
Charged Weight: 19.16 lbs (8.7 kg)
Discharge Time: 11.0 seconds
Flow Rate: 1.45 lb/sec
Effective Range: 10 ft (3 m)
Operating Temperature: -40 °F to 120 °F (-40 °C to 49 °C)
Dimensions: 14.75" H × 9.25" W × 7.125" D
Certifications: Meets ANSI/UL 2129, UL 711, CAN/ULC S508, and S566
Mounting: Requires Ansul hanger hook 432964 (not compatible with standard CLEANGUARD+ wall brackets)